Alarm System - Off-Grid Power

Collapse
X
 
  • Time
  • Show
Clear All
new posts
  • Shockah
    Solar Fanatic
    • Nov 2013
    • 569

    Alarm System - Off-Grid Power

    I'm putting together an Off-Grid Power Supply for an Alarm System install in a remote area with no POCO available.

    The Alarm system is actually DC powered through a 120VAC transformer and has its own 12v7ah back up battery.
    I tried to convince the installer to wire it directly to the Off-Grid DC 12v138ah, (to avoid loss in the inverter and transformer),
    but he insists the system needs to run through the transformer and the assembly needs to be installed as a whole.

    VIA Kill-a-Watt, an identical system consumed a total 180w (120v) over a 24hour period... (average 7.5w per hour)
    In the case of an intruder, the siren will sound and wireless modem will activate, drawing more watts.

    This Off-Grid System absolutely must not fail over the next 3 years.
    ALL Inverters worry me.

    I have put together:
    240w-270w 60Cell Panel (making selection today from local supplier)
    136AH 12v AGM Battery
    Blue Sky SB2512i-HV MPPT CC
    Samlex PST-15S-12A 150W Pure-Sine Inverter
    Minimum 4hour insolation in December.

    Any thoughts on the above listed components?
    Any words of confidence on the Samlex Inverter?

    Thanks!
    [CENTER]SunLight @ Night[/CENTER]
  • pleppik
    Solar Fanatic
    • Feb 2014
    • 508

    #2
    Originally posted by Shockah
    This Off-Grid System absolutely must not fail over the next 3 years.
    ALL Inverters worry me.
    I'm not qualified to comment on how you're building your system, but I've done a little disaster planning and failure analysis in my life.

    Generally speaking, saying that a system "absolutely must not fail" is the wrong way to think about the problem. All systems have some probability of failure, and as you try to push that probability closer to zero, the costs go up exponentially.

    The questions you should be asking yourself are: 1) What probability of failure are you willing to accept? 2) How much are you willing to spend to get there? 3) If something does go wrong, how quickly can someone be there to fix it?

    If this is truly a critical system which has to have a minimum probability of system failure, usually the cheapest way to get there is through redundancy. Put in extra of everything, and design it so that any one component can break and you still can be functional. So extra panels, extra batteries, extra inverters, etc.

    I'm guessing, though, that your real design goal is not "must not fail" but something closer to "as reliable as possible without spending any extra money." That's perfectly reasonable, just make sure your expectations are realistic.
    16x TenK 410W modules + 14x TenK 500W inverters

    Comment

    • Sunking
      Solar Fanatic
      • Feb 2010
      • 23301

      #3
      Originally posted by Shockah
      The Alarm system is actually DC powered through a 120VAC transformer and has its own 12v7ah back up battery.
      I tried to convince the installer to wire it directly to the Off-Grid DC 12v138ah, (to avoid loss in the inverter and transformer),
      but he insists the system needs to run through the transformer and the assembly needs to be installed as a whole
      Then fire the installer because he is incompetent. There is no justification for AC power or an inverter.

      Originally posted by Shockah
      This Off-Grid System absolutely must not fail over the next 3 years.
      Impossible, all off grid systems fail no matter how much money you throw at it. Just 4 or 5 cloudy days and your system is down period unless you have an emergency generator.
      MSEE, PE

      Comment

      • Shockah
        Solar Fanatic
        • Nov 2013
        • 569

        #4
        Originally posted by Sunking
        Then fire the installer because he is incompetent. There is no justification for AC power or an inverter.

        The one who hired him for the alarm hired me for the Solar Power. If I was the one who hired him, I woulda fired him... lol
        I was trying to convince him of eliminating AC, but he insists he needs a 120v outlet for his system to function.

        Impossible, all off grid systems fail no matter how much money you throw at it. Just 4 or 5 cloudy days and your system is down period unless you have an emergency generator.

        If cloudy days are my only worry, then I am not worried about it. I am more concerned about component failure.
        Thanks for your input!
        [CENTER]SunLight @ Night[/CENTER]

        Comment

        • Shockah
          Solar Fanatic
          • Nov 2013
          • 569

          #5
          Originally posted by pleppik
          I'm not qualified to comment on how you're building your system, but I've done a little disaster planning and failure analysis in my life.

          Generally speaking, saying that a system "absolutely must not fail" is the wrong way to think about the problem. All systems have some probability of failure, and as you try to push that probability closer to zero, the costs go up exponentially.

          The questions you should be asking yourself are: 1) What probability of failure are you willing to accept? 2) How much are you willing to spend to get there? 3) If something does go wrong, how quickly can someone be there to fix it?

          If this is truly a critical system which has to have a minimum probability of system failure, usually the cheapest way to get there is through redundancy. Put in extra of everything, and design it so that any one component can break and you still can be functional. So extra panels, extra batteries, extra inverters, etc.

          I'm guessing, though, that your real design goal is not "must not fail" but something closer to "as reliable as possible without spending any extra money." That's perfectly reasonable, just make sure your expectations are realistic.
          Correct, there are no absolutes. But I can't say "I'll be satisfied with 99% fail proof"... I'll do what I can to make it 100% fail proof, and deal with the failures when they present themselves... and learn from the failures/causes.

          The redundancy I will build into the system is a circuit that bypasses the inverter and transformer in case one of them fail.
          As far as the PV Panel, CC or Batteries is concerned, I can have that replaced the same day as the failure.
          The Alarm sends a notification if the back-up battery voltage gets low... which gives me time to respond.

          Thanks for your input.
          [CENTER]SunLight @ Night[/CENTER]

          Comment

          • Shockah
            Solar Fanatic
            • Nov 2013
            • 569

            #6
            0219041432.jpg stainless post topper.jpg

            0226041444.jpg 0226041207.jpg

            I built these Solar Lights for the Property Owner...
            That is how we got to talking about an Alarm System Power Supply...
            Unfortunately, He already has an "Alarm Guy"...
            [CENTER]SunLight @ Night[/CENTER]

            Comment

            • Sunking
              Solar Fanatic
              • Feb 2010
              • 23301

              #7
              Originally posted by Shockah
              Correct, there are no absolutes. But I can't say "I'll be satisfied with 99% fail proof"... I'll do what I can to make it 100% fail proof, and deal with the failures when they present themselves...
              Well take it from a EE who designs critical electrical systems for telecom, data centers, banks, and military what you want is not possible regardless of how much money you dump into it. Switching from commercial power to solar even makes it more difficult and expensive because solar is so much more unreliable and unpredictable.
              MSEE, PE

              Comment

              • Shockah
                Solar Fanatic
                • Nov 2013
                • 569

                #8
                Originally posted by Sunking
                Well take it from a EE who designs critical electrical systems for telecom, data centers, banks, and military what you want is not possible regardless of how much money you dump into it. Switching from commercial power to solar even makes it more difficult and expensive because solar is so much more unreliable and unpredictable.
                The more I work with Off-Grid PV Power, the more I am learning that, Sunking.

                The best I can do is continue the quest of finding combinations of the most reliable components.
                [CENTER]SunLight @ Night[/CENTER]

                Comment

                • Mike90250
                  Moderator
                  • May 2009
                  • 16020

                  #9
                  Your batteries will always be the weak point. Telcoms swap them out on a regular basis. Any battery over 2 years old would be suspect in a critical application. I'd also use AGM batteries. (2, 6v golf cart in series for 12V)

                  The voltage in a PV system will swing from 12v - 15V, and perhaps the alarm tech is concerned that the high recharge voltage will BBQ the alarm gear. That's the only thing I can see. So instead of an inverter (of which I would use the Suresine 300 which is quite robust) you may use a DC-DC supply, and let it make the alarm circuit happy. There are some good Telcom 48-12V adapters, but that means 4, 12V batteries, larger PV & controller. Other 12v-12v adapters are not as robust, methinks.
                  Powerfab top of pole PV mount (2) | Listeroid 6/1 w/st5 gen head | XW6048 inverter/chgr | Iota 48V/15A charger | Morningstar 60A MPPT | 48V, 800A NiFe Battery (in series)| 15, Evergreen 205w "12V" PV array on pole | Midnight ePanel | Grundfos 10 SO5-9 with 3 wire Franklin Electric motor (1/2hp 240V 1ph ) on a timer for 3 hr noontime run - Runs off PV ||
                  || Midnight Classic 200 | 10, Evergreen 200w in a 160VOC array ||
                  || VEC1093 12V Charger | Maha C401 aa/aaa Charger | SureSine | Sunsaver MPPT 15A

                  solar: http://tinyurl.com/LMR-Solar
                  gen: http://tinyurl.com/LMR-Lister

                  Comment

                  • Sunking
                    Solar Fanatic
                    • Feb 2010
                    • 23301

                    #10
                    Originally posted by Mike90250
                    There are some good Telcom 48-12V adapters, but that means 4, 12V batteries,.
                    Also a lot of 24 to 12 volt.
                    MSEE, PE

                    Comment

                    • Shockah
                      Solar Fanatic
                      • Nov 2013
                      • 569

                      #11
                      Originally posted by Mike90250
                      Your batteries will always be the weak point. Telcoms swap them out on a regular basis. Any battery over 2 years old would be suspect in a critical application. I'd also use AGM batteries. (2, 6v golf cart in series for 12V)

                      I am using 2 Odyssey AGM 68amps in Parallel ...
                      No such thing as AGM 6v available here and would cost way too much to ship them in individually.


                      The voltage in a PV system will swing from 12v - 15V, and perhaps the alarm tech is concerned that the high recharge voltage will BBQ the alarm gear. That's the only thing I can see. So instead of an inverter (of which I would use the Suresine 300 which is quite robust) you may use a DC-DC supply, and let it make the alarm circuit happy. There are some good Telcom 48-12V adapters, but that means 4, 12V batteries, larger PV & controller. Other 12v-12v adapters are not as robust, methinks.

                      Thanks for that input. DC-DC sounds viable to me.
                      I believe the Transformer output was 15v.
                      I know for sure the back up battery is 12v7ah.
                      Once the "Alarm" system is installed, I will evaluate it and determine if it can be operated without Inverter/Transformer.
                      Thanks!
                      [CENTER]SunLight @ Night[/CENTER]

                      Comment

                      • Sunking
                        Solar Fanatic
                        • Feb 2010
                        • 23301

                        #12
                        I am using 2 Odyssey AGM 68amps in Parallel ...
                        No such thing as AGM 6v available here and would cost way too much to ship them in individually.


                        Don't do that, just one one single battery. Odyssey makes a 120 AH @ 20 hour rate in a 12 volt battery. At your discharge rate more like 160 AH. PC2250
                        MSEE, PE

                        Comment

                        • Mike90250
                          Moderator
                          • May 2009
                          • 16020

                          #13
                          Originally posted by Shockah
                          No such thing as AGM 6v available here and would cost way too much to ship them in individually.
                          No golf courses on that island ? But there are some nearby? The batteries will be the thing you don't want to skimp on, (well, if it's mission critical, skimp on nothing)
                          Just be sure the ones you get are indeed AGM, not GEL, they are different beasts.
                          Powerfab top of pole PV mount (2) | Listeroid 6/1 w/st5 gen head | XW6048 inverter/chgr | Iota 48V/15A charger | Morningstar 60A MPPT | 48V, 800A NiFe Battery (in series)| 15, Evergreen 205w "12V" PV array on pole | Midnight ePanel | Grundfos 10 SO5-9 with 3 wire Franklin Electric motor (1/2hp 240V 1ph ) on a timer for 3 hr noontime run - Runs off PV ||
                          || Midnight Classic 200 | 10, Evergreen 200w in a 160VOC array ||
                          || VEC1093 12V Charger | Maha C401 aa/aaa Charger | SureSine | Sunsaver MPPT 15A

                          solar: http://tinyurl.com/LMR-Solar
                          gen: http://tinyurl.com/LMR-Lister

                          Comment

                          • Wy_White_Wolf
                            Solar Fanatic
                            • Oct 2011
                            • 1179

                            #14
                            Wiring the alarm without the inverter could void the warrantee on it. I'd say the installer is just covering his ass should anything go wrong.

                            WWW

                            Comment

                            • Shockah
                              Solar Fanatic
                              • Nov 2013
                              • 569

                              #15
                              Originally posted by Sunking

                              Don't do that, just one one single battery. Odyssey makes a 120 AH @ 20 hour rate in a 12 volt battery. At your discharge rate more like 160 AH. PC2250
                              I knew I'd get backlash for the 2xparallel set-up...
                              but really the only way with local suppliers I can obtain the needed 140ish AH with AGM.

                              No PC2250 available locally... the only other Ody sold locally is the 100AH PC2150... but out of stock.

                              The Interstate Batteries Distributor has a PC2150 equivalent for $500+++
                              When asked what the AH rating is, he told me they don't sell batteries by AH... they sell them by CCA.
                              I refuse to deal with them.

                              I have more confidence in parallel than I do Interstate.

                              Originally posted by Mike90250
                              No golf courses on that island ? But there are some nearby? The batteries will be the thing you don't want to skimp on, (well, if it's mission critical, skimp on nothing)
                              Just be sure the ones you get are indeed AGM, not GEL, they are different beasts.
                              Seriously, All the 6volt batteries I have found locally are Flooded.
                              The cost to freight anything of that weight here is absurd.
                              Another important factor is replacement availability.

                              *Limited Selection of Deep Cycle Batteries is a price we pay to live in the middle of the Pacific.... and it sucks.
                              [CENTER]SunLight @ Night[/CENTER]

                              Comment

                              Working...